ACE8000 FAS

Ripple Control Filter

To find your local sales contact

ACE8000 FAS - Click to enlarge
Ripple Control Filter

 

Attached documents

   » Product brochures
Electrical utilities use distribution networks to transmit information such as tariff change and load control commands to end-users by injecting signals at low frequencies at the HV/MV substations level (ripple control system).

Independent power producers connected to the MV network change its impedance and may disturb the level of the signals. 
 
The FAS Active filter is designed to permit an independent power producer to connect to the MV distribution network by efficiently filtering ripple control signals. It prevents the power generators disturbing the ripple control commands sent by the utility from the HV/MV substation.  

It works by injecting in the IPP connecting feeder a signal at the ripple control frequency equal in phase and magnitude to the signal measured on the MV network.

This stops the current at the ripple control frequency going into the power generators and maintains the ripple control signals at their original values (before power generators' connection).
Benefits
  • Facilitates connection - authorisation of the IPP to the MV network
  • Suitable for a 2-frequency ripple control system
  • No risk of disconnection of the IPP by the Utility
  • Regular efficiency checks unnecessary


Key Features
  • Suitable for IPP connected to MV network voltage:10-15-20 kV
  • Power Range :
    • FAS2500 for IPP <2.5 MVA
    • FAS12 for IPP <12 MVA 
    • FAS20 for IPP <20 MVA
  • Dual frequency (175-188 Hz) 
  • Remote reading of ripple control measures and internal fault diagnosis
  • Loss at 50 Hz lower than 2kW
  • Minimal voltage drop at 50Hz 
  • Resists short-circuit current of 12,500 A
  • Reduced dimensions
 